Common error 1. The oil temperature is too high: reason: (1) The cooling capacity of the oil cooler is reduced. (2) The supply of refrigerant for cooling the oil cooler is insufficient due to clogging of the refrigerant filter screen. (3) Bearing wear. solution: (1) Adjust the oil temperature...
Send Inquiry
Product Introduction

 

 

 

 

Product Features

Automatic,Energy saving,Customizable,High-accuracy,High Productivity

Service

Sample testing support,Free technical consultation service

Sale offer

Competitive pric

 

 

Common error

1. The oil temperature is too high:

reason:

(1) The cooling capacity of the oil cooler is reduced.

(2) The supply of refrigerant for cooling the oil cooler is insufficient due to clogging of the refrigerant filter screen.

(3) Bearing wear.

solution:

(1) Adjust the oil temperature control valve.

(2) Clean the filter screen of the refrigerant filter.

(3) Repair or replace the bearing after disassembly.


2.Main motor overload:

reason:

(1) The power phase voltage is unbalanced.

(2) The voltage drop of the power supply line is large.

(3) The amount of cooling refrigerant supplied to the main motor is insufficient.

solution:

(1) Take measures to balance the power phase voltage.

(2) Take measures to reduce the voltage drop of the power supply line.

(3) Check the filter screen of the refrigerant filter and clean the filter screen; open the large refrigerant inlet valve

 

Maintenance

The sequence of opening and stopping the chiller To ensure that the air-conditioning host can operate normally after starting, it must be ensured that:

① The condenser has good heat dissipation, otherwise it will cause the chiller high-pressure protection device to act and stop due to the excessively high condensing temperature and corresponding condensing pressure, or even cause a malfunction.

②The cold water in the evaporator should circulate, otherwise the cold water temperature protection device will stop due to the low temperature of the cold water, or the low pressure protection device of the chiller will stop due to the low evaporation temperature and corresponding evaporation pressure, or even Cause the cold water in the evaporator to freeze and damage the equipment. Therefore, the sequence of starting the chiller is: (must be strictly followed) Cooling tower fan is on -> cooling water pump is on -> chilled water pump is on -> the chiller is on. The stopping sequence of the chiller is: (must be strictly followed) Stop-->Cooling tower fan stopped-->Cooling water pump stopped-->Cold water pump stopped

 

Precautions

① When shutting down, the chiller should be shut down half an hour before the end of get off work, and the chiller pump should be shut down after get off work, which is conducive to saving energy, while avoiding downtime and protecting the unit.

② Before running the refrigeration cycle, confirm that all valves of the heating cycle pipeline are closed.

 